Fault Index,Fault Code,Error Message,Remedy,Further Steps and Checks ,,,, 0,0.0,Input Fault,Cycle Input,Check for unstable input signal or turn input OFF to clear the fault indication 1,1.1,Output Fault,Check for shorts,A safety output appears ON at power-up when it should be OFF so check for a short to an external voltage source. 2,1.2,Output Fault,Check for shorts,"A safety output is sensing a fault to another voltage source so check for shorts between safety outputs, a short to an external voltage source, or check the load device compatibility." 3,1.3,Internal Fault,Contact Banner Engineering, 4,1.4,Internal Fault,Contact Banner Engineering, 5,1.5,Internal Fault,Contact Banner Engineering, 6,1.6,Internal Fault,Contact Banner Engineering, 7,1.7,Output Fault,Check for shorts,An overload is detected on the safety outputs so check each output terminal for a short to ground or verify the system power supply rating. 8,1.8,Internal Fault,Contact Banner Engineering, 9,2.1,Concurrency Fault,Cycle Input,"One input of a dual-channel input went to the Stop state then back to Run so check the input signals, the wiring, or consider adjusting the input debounce times." 10,2.2,Simultaneity Fault,Cycle Input,One input of a dual-channel input went to the Run state but the other input did not follow in 3 seconds so check the input signal timing or the wiring. 11,2.3,Concurrency Fault,Cycle Input,"One input of a complementary pair went to the Stop state then back to Run so check the input signals, the wiring, or consider adjusting the input debouce times." 12,2.4,Simultaneity Fault,Cycle Input,One input of a complementary pair went to the Run state but the other input did not follow in 3 seconds so check the input signal timing or the wiring. 13,2.5,Concurrency Fault,Cycle Input,"One input of a complementary pair went to the Stop state then back to Run so check the input signals, the wiring, or consider adjusting the input debouce times." 14,2.6,Simultaneity Fault,Cycle Input,One input of a complementary pair went to the Run state but the other input did not follow in 3 seconds so check the input signal timing or the wiring. 15,2.7,Internal Fault,Contact Banner Engineering, 16,2.8,Input Fault,Check Input Terminals,An input is stuck high so check for shorts to other inputs or other voltage source or check the input device compatibility. 17,2.9,Input Fault,Check Input Terminals,An input is stuck high so check for shorts to other inputs or other voltage source or check the input device compatibility. 18,2.10,Input Fault,Check Input Terminals,Check for a short between inputs. 19,2.11,Input Fault,Check Input Terminals,Check for a short to ground. 20,2.12,Input Fault,Check Input Terminals,Check for a short to ground. 21,2.13,Input Fault,Check Input Terminals,An input is stuck low so check for a short to ground. 22,2.14,Input Fault,Check Input Terminals,An input is missing test pulses so check for a short to other inputs or other voltage source. 23,2.15,Open Lead,Check Input Terminals,Check for an open lead. 24,2.16,Input Fault,Check Input Terminals,An input is missing test pulses so check for a short to other inputs or other voltage source. 25,2.17,Input Fault,Check Input Terminals,An input is missing test pulses so check for a short to other inputs or other voltage source. 26,2.18,Input Fault,Check Input Terminals,An input is missing test pulses so check for a short to other inputs or other voltage source. 27,2.19,Open Lead,Check Input Terminals,Check for an open lead. 28,2.20,Input Fault,Check Input Terminals,An input is missing test pulses so check for a short to ground. 29,2.21,Open Lead,Check Input Terminals,Check for an open lead. 30,2.22,Input Fault,Check Input Terminals,Check for an unstable signal on the input. 31,2.23,Input Fault,Check Input Terminals,Check for an unstable signal on the input. 32,3.1,EDM Fault,Check EDM Terminals,An EDM contact is open prior to turning ON the safety outputs so check for a stuck-ON contactor or relay or check for an open wire. 33,3.2,EDM Fault,Check EDM Terminals,An EDM contact failed to close within 200 ms after the safety outputs turned OFF so check for slow or stuck-ON contactor or relay or check for an open wire. 34,3.3,EDM Fault,Check EDM Terminals,An EDM contact is open prior to turning ON the safety outputs so check for a stuck-ON contactor or relay or check for an open wire. 35,3.4,EDM Fault,Check EDM Terminals,An EDM contact pair mismatched for longer than 200 ms so check for slow or stuck-ON contactor or relay or check for an open wire. 36,3.5,EDM Fault,Check EDM Terminals,Check for an unstable signal on the input. 37,3.6,EDM Fault,Check EDM Terminals,Check for a short to ground. 38,3.7,EDM Fault,Check EDM Terminals,Check for a short between inputs. 39,4.1,Supply Voltage Low,Check Power Supply,The supply voltage dropped below the rated voltage for longer than 6 ms so check the power supply voltage and current rating or check for an overload on the outputs that might cause the power supply to limit the current. 40,4.2,Internal Fault,Contact Banner Engineering, 41,4.3,Internal Fault,Contact Banner Engineering, 42,4.4,Internal Fault,Contact Banner Engineering, 43,4.5,Internal Fault,Contact Banner Engineering, 44,4.6,Internal Fault,Contact Banner Engineering, 45,4.7,Internal Fault,Contact Banner Engineering, 46,4.8,Internal Fault,Contact Banner Engineering, 47,4.9,Internal Fault,Contact Banner Engineering, 48,4.10,Internal Fault,Contact Banner Engineering, 49,4.11,Internal Fault,Contact Banner Engineering, 50,4.12,Configuration Timeout,Check Configuration,The Safety Controller was left in Configuration Mode for more than one hour without pressing any keys. 51,4.13,Configuration Timeout,Check Configuration,The Safety Controller was left in Configuration Mode for more than one hour without receiving any command from the PC Interface. 52,4.14,Configuration Unconfirmed,Confirm Configuration,The configuration was not confirmed after being edited. 53,4.15,Internal Fault,Contact Banner Engineering, 54,4.16,Internal Fault,Contact Banner Engineering, 55,4.17,Internal Fault,Contact Banner Engineering, 56,4.18,Internal Fault,Contact Banner Engineering, 57,4.19,Internal Fault,Contact Banner Engineering, 58,4.20,Unassigned Terminal in Use,Check Terminals,This terminal is not assigned to any device in the present configuration and should not be active so check the wiring. 59,4.21,Internal Fault,Contact Banner Engineering, 60,4.22,Internal Fault,Contact Banner Engineering, 61,4.23,Internal Fault,Contact Banner Engineering, 62,4.24,Internal Fault,Contact Banner Engineering, 63,4.25,Internal Fault,Contact Banner Engineering, 64,4.26,Internal Fault,Contact Banner Engineering, 65,4.27,Internal Fault,Contact Banner Engineering, 66,4.28,Internal Fault,Contact Banner Engineering, 67,4.29,Internal Fault,Contact Banner Engineering, 68,4.30,Internal Fault,Contact Banner Engineering, 69,4.31,Internal Fault,Contact Banner Engineering, 70,4.32,Internal Fault,Contact Banner Engineering, 71,5.1,Mute Lamp Fault,Check Lamp and Wiring,"The monitored status output voltage should be low when the lamp is OFF and is sensing a high, indicating an open in the mute lamp circuit." 72,5.2,Mute Lamp Fault,Check for shorts,"The monitored status output voltage should be high when the lamp is ON and is sensing a low, indicating a short in the mute lamp circuit." 73,5.3,Internal Fault,Contact Banner Engineering, 74,6.xx,Internal Fault,Load New Configuration,Invalid configuration data was detected so load a new configuration. 75,4.33,Internal Fault,Contact Banner Engineering,